Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
A-20
PLINE_STATUS 78 1.Inactive
2.Learning
3.Verifying
4.All Lines
Plugged
5.OK
6.Insufficient
Dynamics
7.BAD PV Status
8.Not Licensed
Inactive N/A Read
Only
Last Impulse line status
PLINE_
TIMESTAMP
79 All Times and
Dates
0 Read
Only
Last Timestamp for PLINE_STATUS
PLINE_ON 80 0 = FALSE
0xff = TRUE
FALSE N/A Turns algorithm On/Off
PLINE_
RELEARN
81 1. Run
2. Relearn
1 N/A Resets the algorithm and reinitiates learning
PLINE_
SENSITIVITY
82 1. Low
2. Medium
3. High
Medium N/A Detection Sensitivity
PLINE_AFFECT_
PV_STATUS
83 0 = FALSE
0xff = TRUE
FALSE N/A Determines whether the quality of the pressure measurement
will be affected or unaffected when a plugged impulse line is
detected
PLINE_HISTORY
_STATUS
84 1. Lines Plugged
2. No History
3 N/A Read
Only
Last plugged Line determination status
PLINE_HISTORY
_TIMESTAMP
85 All Times and
Dates
0 Read
Only
Timestamp of last plugged impulse line detection
PLINE_LEARN_
LENGTH
86 1 to 45 5 Min. Length of Learning and Verification Cycles in Minutes
PLINE_DETECT
_LENGTH
87 1 to 45 1 Min. Length of Detection Cycle Status Update in Minutes
PLINE_AUTO_
RELEARN
88 0 = Disabled
0xff = Enabled
Enabled Enables/Disables Auto Relearn on Process Mean Changes
PLINE_RELEAR
N_THRESHOLD
89 0 to 50 0.0 %URL Threshold for Relearning in % Primary Value URL of Sensor
PLINE_LEARNIN
G_SENSITIVITY
90 1. Insufficient
Dynamics Check
2. 10%
StdevChange
Check
3. 20% Stdev
Change Check
4. 30% Stdev
Change Check
5. 3*Stdev Mean
Change Check
6. 6*Stdev Mean
Change Check
7. 2% Mean
Change Check
0x55 Learning Sensitivity Check Options. Only one of bits 2, 3 and 4
is allowed and only one of bits 5 and 6 is allowed.
PLINE_DETECT
_SENSITIVITY
91 0 to 100 0.0 % Overrides IL Plugging Sensitivity if a non-zero value is
entered. Value corresponds to a percentage decrease in
standard deviation.
PLINE_SINGLE_
DETECT_
SENSITIVITY
92 0 to 10000 0.0 % Overrides IL Plugging Sensitivity if a non-zero value is
entered. Value corresponds to a percentage increase in
standard deviation. (Used by DP transmitters only)
Parameter Index Valid Range Initial Value Units Other Description